Modifications to positioner firmware compared to the previous version
1.41 (old) 1.42 (new)
After performing a reset to default values, the allocation of the closing position AIR
TO OPEN (AtO) /AIR TO CLOSE (AtC) is not reset to the default setting. The setting is
kept.
1.42 (old) 1.51 (new)
All EXPERTplus diagnostic functions are available in the positioner without having to
activate them first (refer to EB 8389 EN on EXPERTplus valve diagnostics)
Optional binary input with following actions:
– Transfer switching state
– Set local operation write protection
– Switch between AUTO/MAN
– Various diagnostic functions (refer to EB 8389 EN on EXPERTplus valve diagnos
-
tics).
The pressure limit (Code 16) is no longer automatically set during initialization.
1.51 (old) 1.52 (new)
Internal modifications