Press , Code 36 blinks
Turn
Std
Press . All start-up parameters and the di
-
agnosis are reset to their default values.
Note:
Code 36 - diAG allows just the diagnosis
data (EXPERTplus) to be reset. Refer to
EB 8389 EN on EXPERTplus valve diag
-
nostics.
Reset the control and identification pa
-
rameters as well as the bus address with
the FACTORY_RESET parameter (refer to
Configuration Manual KH 8384-4 EN).
7.9 Start-up via local interface
(SSP)
The positioner can either be commissioned,
configured, and operated on site, using the
Fieldbus configuration or operating system,
or TROVIS-VIEW operator interface con
-
nected over the serial interface in the
positioner.
Use the TROVIS-VIEW software with 3730-4
device module installed.
To connect the positioner directly to the PC
via the local serial interface, an adapter (or
-
der no. 1400-7700) is required.
The positioner can be supplied with power
by connecting it to a fieldbus segment or
over a DC voltage source (9 to 32 V) con
-
nected to the bus terminals in the positioner.
The simultaneous operation of
TROVIS-VIEW and the fieldbus system is
possible without any restrictions when con
-
nected to a PROFIBUS-PA segment.
7.10 Setting the bus address
A maximum of 32 positioners in a safe
(non-hazardous) area can be operated over
a segment coupler in one PROFIBUS-PA seg
-
ment.
Each positioner connected in the segment
must be assigned a unique bus address be
-
tween 0 and 125.
Default 126
Turn
Code 3, display: No
Press , Code 3 blinks.
Change the setting of Code 3.
Turn
YES
Press , display:
The configuration is enabled.
Turn
Code
46, press ,
turn
required address,
press 10 seconds
The address is
adopted straightaway, provided that cyclic
data exchange is not taking place.
During the cyclic data exchange, the newly
set address for the positioner is saved and
adopted after the cyclic data exchange is
finished.
The newly assigned address is indicated un
-
der Code 46 in alternating sequence with
the current address. The new address is
marked with “n“ (new) and the currently
used address with “o“ (old).
EB 8384-4 EN 69
Start-up Settings