Code
no.
Parameter – Display, values
[default setting]
Description
Note: Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
9*
Travel/angle range end
(upper x-range value)
20.0 to 100.0 [100.0] % of
the nominal range
ESC
Note: Specified in mm or
angle ° provided Code 4 is
set
Upper range value for the travel/angle of rotation in the nominal
or operating range.
Value is displayed or must be entered.
The characteristic is adapted.
Example: The operating range is modified, for example, to limit
the range of a control valve which has been sized too large. For
this function, the entire resolution range of the set point is con
-
verted to the new limits. 0 % on the display corresponds to the
adjusted lower limit and 100 % to the adjusted upper limit.
10*
Travel/angle lower limit
(lower x-limit)
0.0 to 49.9 % of the
operating range
[No], ESC
Limitation of the travel/angle of rotation downwards to the en
-
tered value, the characteristic is not adapted.
The characteristic is not adapted to the reduced range. See also
example in Code 11.
11*
Travel/angle upper limit
(upper x-limit)
50.0 to 120.0 [100] % of
the operating range
No, ESC
Limitation of the travel/angle of rotation upwards to the entered
value, the characteristic is not adapted.
Example: In some applications, it is better to limit the valve
travel, e.g. if a certain minimum medium flow is required or a
maximum flow must not be reached.
The lower limit must be adjusted with Code 10, and the upper
limit with Code 11.
If a tight-closing function has been set up, it has priority over the
travel limitation!
When set to No, the valve can be opened past the nominal travel
with a set point outside of the 0 to 100 % range.
14*
Set point range start
(w-start)
0.0 to 49.9 [1.0] %
of the span adjusted via
Code 12/13
No, ESC
If w approaches the percentage adjusted at the final value that
causes the valve to close, the actuator is immediately completely
vented (with AIR TO OPEN) or filled with air (with AIR TO
CLOSE). This action always lead to maximum tight-closing of the
valve.
Codes 14/15 have priority over Codes 8/9/10/11.
Codes 21/22 have priority over Codes 14/15.